Menu 7 − Analog I/O

Mode: RFC‑S

The diagram below shows the parameter structure for each I/O. See Internal I/O Identifier (11.068) for details of which I/O is present for different I/O options. 

Analog Outputs
The update rate for analog outputs is 250μs; although the output will only change at the update rate defined by the source parameter for the output. The following exceptions apply:

  1. Speed Feedback (03.002) has an update rate of 4ms and includes a 16ms window filter. If this parameter is selected as a source for output 2 the update rate of the source changes to 250us and the only filter applied is the window filter associated with the position feedback interface (i.e. P1 Feedback Filter (03.042) for the P1 interface). It should be noted that this feature is only provided when the position feedback is from a drive interface and not from an option module.
  2. If either analogue output is set up for current mode then the update rate for both analogue outputs is 4ms.

Analog Inputs
The normal sample rate for the analog inputs is 4ms, however this is increased to 250us for analogue inputs 1 and 2 under the following conditions:

  1. The maximum and the minimum for the input are at their default values of 100.00% and -100.00% respectively.
  2. The input is set to voltage mode.
  3. One of the destinations given in the table below must be selected.
  4. If the destination is Hand Mode Analog Reference (01.036) or Analog Reference 2 (01.037) the reference system must not be in uinpolar mode, i.e. Bipolar Reference Enable (01.010) must be one.

Note that Analog Input 1 Fast Update Active (07.026) and Analog Input 2 Fast Update Active (07.027) indicate if fast updating is active for each input.

Parameter Drive modes Comment
Hand Mode Analog Reference (01.036) RFC-A, RFC-S The data from Hand Mode Analog Reference (01.036) is processed in the 250us task so that the reference to the speed controller is updated every 250us. 

 


Parameter07.001  Analog Input 1 (T5)
Short descriptionDisplays the value of analog input 1
ModeRFC‑S
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate250µs write
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

Each analogue input has a resolution of 11 bits plus sign. The inputs can operate in different modes (defined by Analog Input 1 Mode (07.007) for analogue input 1). These modes include voltage, current and thermistor modes. The available modes depend on the hardware configuration and are given in the table below. 

Internal I/O Identifier (11.068) Analogue Input 1 Analogue Input 2 Analogue Input 3
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage, Current Bipolar Voltage, Current Bipolar Voltage, Thermistor
1: Digital I/O (M702) Not present Not present Thermistor, Disabled
2: HVAC Analogue and Digital I/O Unipolar Voltage, Current, Thermistor Unipolar Voltage, Current, Thermistor Not present

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage / 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA ((20mA - Input Current) / 20mA) x 100.00%
4-20mA ((Input Current - 4mA) / 16mA) x 100.00%
20-4mA ((20mA - Input Current) / 16mA) x 100.00%
Thermistor (Input resistance / 10kΩ ) x 100%

Analog Input 1 (07.001) is derived as follows:

Limits
A1 is the value after the minimum and maximum limits are applied.

If Analog Input 1 Minimum (07.040) ≥ Analog Input 1 Maximum (07.043) then:
A1 = 0.00% whatever the input level.

If Analog Input 1 Minimum (07.040) < 0.00% and Analog Input 1 Maximum (07.043) > 0.00% then:
A1 = Input Level x (100.00% / Analog Input 1 Maximum (07.043))
A1 is then limited between -100% and +100%.

Otherwise:
Input Level is limited between Analog Input 1 Minimum (07.040) and Analog Input 1 Maximum (07.043)
A1 = [Input Level - Analog Input 1 Minimum (07.040)] x 100.00% / (Analog Input 1 Maximum (07.043) - Analog Input 1 Minimum (07.040))

For thermistor modes it should be noted that Analog Input 1 Minimum (07.040) and Analog Input 2 Minimum (07.041) have no effect and that the input resistance is limited between 0 and 5kΩ.


Parameter07.002  Analog Input 2 (T6)
Short descriptionDisplays the value of analog input 2
ModeRFC‑S
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate250µs write
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

Analog Input 2 (07.002) shows the level of analogue input 2. See Analog Input 1 (07.001) for more information.


Parameter07.004  Monitored Temperature 1
Short descriptionDisplays the temperature set up by Temperature Monitor Select 1
ModeRFC‑S
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Thermal monitoring is provided within the drive to protect the power stage and the control system from over temperature.

Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006) give an indication of the temperature of three selected monitoring points within the drive power system or control system. The required monitoring points can be selected using the monitor select parameters Temperature Monitor Select 1 (07.038), Temperature Monitor Select 2 (07.039) and Temperature Monitor Select 3 (07.052) respectively. The default values give two monitoring points in the power system in Monitored Temperature 1 (07.004) = 01001 and Monitored Temperature 2 (07.005) = 01002, and control board temperature 1 in Monitored Temperature 3 (07.006) = 00001.

The following table shows the value to be entered into the monitor select parameters to select the required monitoring point. If the monitoring point selected does not exist then the monitored temperature is always zero.

Source xx y zz
Control system 00 0 01: Control board thermistor 1
Control system 00 0 02: Control board thermistor 2
Control system 00 0 03: I/O board thermistor (or internal braking resistor in Servo Drive)
Control system 00 1 00: Inverter thermal model
Control system 00 3 00: Braking IGBT thermal model
Control system 00 4 00: Rectifier thermal model
Power system 01 0 zz: Thermistor location defined by zz in the power system
Power system 01       Rectifier number zz: Thermistor location defined by zz in the rectifier

For a multi-module power system the power system measurement that can be selected is shown in the table below. It should be noted that the specific power module cannot be selected and that the highest temperature from each of the power modules is given.

Source xx y zz
Power system 01       0      01: U phase power device thermistor
Power system 01 0 02: V phase power device thermistor
Power system 01 0 03: W phase power device thermistor
Power system 01 0 04: General rectifier thermistors
Power system 01 0 05: General power system thermistor


Parameter07.005  Monitored Temperature 2
Short descriptionDisplays the temperature set up by Temperature Monitor Select 2
ModeRFC‑S
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Monitored Temperature 1 (07.004) for details.


Parameter07.006  Monitored Temperature 3
Short descriptionDisplays the temperature set up by Temperature Monitor Select 3
ModeRFC‑S
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Monitored Temperature 1 (07.004) for details.


Parameter07.007  Analog Input 1 Mode (T5)
Short descriptionDefines the mode of analog input 1
ModeRFC‑S
Minimum-4Maximum9
Default4Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
-44-20mA Low4-20mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 4-20mA setting.)
-320-4mA Low20-4mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 20-4mA setting.)
-24-20mA Hold4-20mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
-120-4mA Hold20-4mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
00-20mA0-20mA
120-0mA20-0mA
24-20mA Trip4-20mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
320-4mA Trip20-4mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
44-20mA4-20mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
520-4mA20-4mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
6VoltVoltage
7Therm Short CctTemperature measurement input with short circuit detection
8ThermistorTemperature measurement without short circuit detection
9Therm No TripTemperature measurement input with no trips

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

This parameter defines the possible input modes for analog input 1. By default it is set up in 4-20mA for connection to suitable feedback device to the main process PID1 when used in a Pump or Fan system.


Parameter07.008  Analog Input 1 Scaling (T5)
Short descriptionDefines the scaling factor of analog input 1
ModeRFC‑S
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

Analog Input 1 (07.001) is modified by Analog Input 1 Scaling (07.008), Analog Input 1 Offset (07.030) and Analog Input 1 Invert (07.009) before it is routed to its destination as follows:

A1O = Analog Input 1 (07.001) + Analog Input 1 Offset (07.030)

A1O is the value after the offset has been applied and is limited between -100.00% and 100.00%

A1S = A1O x Analog Input 1 Scaling (07.008)

A1S is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%

If Analog Input 1 Invert (07.009) = 0 then A1I = A1S otherwise A1I = -A1S

A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by Analog Input 1 Destination (07.010).


Parameter07.009  Analog Input 1 Invert (T5)
Short descriptionInverts the signal for analog input 1
ModeRFC‑S
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

See Analog Input 1 Scaling (07.008).


Parameter07.010  Analog Input 1 Destination (T5)
Short descriptionDefines the output parameter for analog input 1
ModeRFC‑S
Minimum0.000Maximum59.999
Default29.034Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatMenu Param NumericDecimal Places3
CodingRW, DE, PT, BU

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

See Analog Input 1 Scaling (07.008).


Parameter07.011  Analog Input 2 Mode (T6)
Short descriptionDefines the mode for analog input 2
ModeRFC‑S
Minimum-4Maximum9
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
-44-20mA Low4-20mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 4-20mA setting.)
-320-4mA Low20-4mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 20-4mA setting.)
-24-20mA Hold4-20mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
-120-4mA Hold20-4mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
00-20mA0-20mA
120-0mA20-0mA
24-20mA Trip4-20mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
320-4mA Trip20-4mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
44-20mA4-20mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
520-4mA20-4mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
6VoltVoltage
7Therm Short CctTemperature measurement input with short circuit detection
8ThermistorTemperature measurement without short circuit detection
9Therm No TripTemperature measurement input with no trips

By default, analog input 2 T6 is routed to the Pump and Fan software to provide an analog Hand mode reference via Hand Mode Analog Reference (01.036).

This parameter defines the possible input modes for analog input 2.


Parameter07.012  Analog Input 2 Scaling (T6)
Short descriptionDefines the scaling factor for analog input 2
ModeRFC‑S
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

By default, analog input 2 T6 is routed to the Pump and Fan software to provide an analog Hand mode reference via Hand Mode Analog Reference (01.036).

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.013  Analog Input 2 Invert (T6)
Short descriptionInverts the signal for analog input 2
ModeRFC‑S
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

By default, analog input 2 T6 is routed to the Pump and Fan software to provide an analog Hand mode reference via Hand Mode Analog Reference (01.036).

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.014  Analog Input 2 Destination (T6)
Short descriptionDefines the output parameter for analog input 2
ModeRFC‑S
Minimum0.000Maximum59.999
Default1.036Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatMenu Param NumericDecimal Places3
CodingRW, DE, PT, BU

By default, analog input 2 T6 is routed to the Pump and Fan software to provide an analog Hand mode reference via Hand Mode Analog Reference (01.036).

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.019  Analog Output 1 Source (T7)
Short descriptionDefines the input parameter for analog output 1
ModeRFC‑S
Minimum0.000Maximum59.999
Default3.002Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatMenu Param NumericDecimal Places3
CodingRW, PT, BU

Analog Output 1 Source (07.019) defines the source parameter for analog output 1. The value of the source parameter is scaled with Analog Output 1 Scaling (07.020) and if the scaling is greater than 1.000 the value is clamped between -100% and +100% or between 0% and 100% depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules for parameter routing do not apply, but the scaling always makes -100% to +100% correspond to the range from minus source parameter maximum to plus source parameter maximum, and 0% corresponds to the source parameter value of zero. This means for example that a parameter with a minimum of 1 and a maximum of 10 will produce an output that changes from 10% to 100% as the parameter is change from minimum to maximum.

The outputs provided with different hardware are given in the table below.

Internal I/O Identifier (11.068) Analogue Output 1 Analogue Output 2
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage Bipolar Voltage
1: Digital I/O (M702) No output No output
2: HVAC Analogue and Digital I/O (F300, F600, H300) Unipolar Voltage or Current Unipolar Voltage or Current

Unless the resolution of the output is limited by the source parameter, the resolution of the analogue outputs is 10 bit plus sign.


Parameter07.020  Analog Output 1 Scaling (T7)
Short descriptionDefines the scaling factor for analog output 1
ModeRFC‑S
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog Output 1 Source (07.019).


Parameter07.021  Analog Output 1 Mode (T7)
Short descriptionDefines the mode of analog output 1
ModeRFC‑S
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Volt
10-20mA
220-0mA
34-20mA
420-4mA

Analog Output 1 Mode (07.021) defines the output mode for analogue output 1

Analog Output 1 Mode (07.021) Output type
Volt 0V to + 10V
0-20mA 0mA to 20mA
20-0mA 20mA to 0mA
4-20mA 4mA to 20mA
20-4mA 20mA to 4mA


Parameter07.022  Analog Output 2 Source (T8)
Short descriptionDefines the input source for analog output 2
ModeRFC‑S
Minimum0.000Maximum59.999
Default4.002Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatMenu Param NumericDecimal Places3
CodingRW, PT, BU

Analog Output 2 Source (07.022) defines the source parameter for analog output 2. The value of the source parameter is scaled with Analog Output 2 Scaling (07.023) and if the scaling is greater than 1.000 the value is clamped between -100% and +100% or between 0% and 100% depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules for parameter routing do not apply, but the scaling always makes -100% to +100% correspond to the range from minus source parameter maximum to plus source parameter maximum, and 0% corresponds to the source parameter value of zero. This means for example that a parameter with a minimum of 1 and a maximum of 10 will produce an output that changes from 10% to 100% as the parameter is change from minimum to maximum.

The outputs provided with different hardware are given in the table below.

Internal I/O Identifier (11.068) Analogue Output 1 Analogue Output 2
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage Bipolar Voltage
1: Digital I/O (M702) No output No output
2: HVAC Analogue and Digital I/O (F300, F600, H300) Unipolar Voltage or Current Unipolar Voltage or Current


Parameter07.023  Analog Output 2 Scaling (T8)
Short descriptionDefines the scaling factor for analog output 2
ModeRFC‑S
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog Output 2 Source (07.022).


Parameter07.024  Analog Output 2 Mode (T8)
Short descriptionDefines the mode of analog output 2
ModeRFC‑S
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Volt
10-20mA
220-0mA
34-20mA
420-4mA

Analog Output 2 Source (07.022) defines the output mode for analogue output 2

Analog Output 2 Mode (07.024) Output type
Volt 0V to + 10V
0-20mA 0mA to 20mA
20-0mA 20mA to 0mA
4-20mA 4mA to 20mA
20-4mA 20mA to 4mA


Parameter07.025  Calibrate Analog Input 1 Full Scale (T5)
Short descriptionCalibrates the input level for analog input 1
ModeRFC‑S
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, NC

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

For analog input 1, and in voltage mode only, the full scale value used to determine the input level can be changed from 10V by calibrating the input. The calibration process is triggered by setting Calibrate Analog Input 1 Full Scale (07.025) to one. Calibrate Analog Input 1 Full Scale (07.025) is cleared automatically when the calibration process is complete. After calibration the actions are as follows:

Input voltage during calibration Result
V < 1.5V The calibration result is ignored and the full scale is set to 10V. Analog Input 1 Full Scale (07.051) is set to zero.
1.5V < V < 2.5V The calibration result is ignored and the full scale or Analog Input 1 Full Scale (07.051) are not affected.
V > 2.5V The calibration result is used to set full scale and the value is also stored in Analog Input 1 Full Scale (07.051).

It should be noted that Analog Input 1 Full Scale (07.051) is a power-down save parameter, and so the result is automatically retained after power-down.


Parameter07.026  Analog Input 1 Fast Update Active (T5)
Short descriptionAnalog Input 1 Fast Update Active
ModeRFC‑S
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

By default, analog input 1 T5 is routed to the Pump and Fan software analog feedback input parameter PID Feedback Percent (29.034).

Analog Input 1 Fast Update Active (07.026) is one if the destination for analogue input 1 is being updated at the fast rate of 250us.


Parameter07.027  Analog Input 2 Fast Update Active (T6)
Short descriptionAnalog Input 2 Fast Update Active
ModeRFC‑S
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 2 Fast Update Active (07.027) is one if the destination for analogue input 2 is being updated at the fast rate of 250us.


Parameter07.028  Analog Input 1 Current Loop Loss (T5)
Short descriptionDisplays when analog input 1 falls below 3mA
ModeRFC‑S
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

By default, analog input 1 T5 is routed to the Pump software analog feedback input parameter PID Feedback Percent (29.034). This parameter provides feedback to the Pump and Fan software on the integrity of the main process PID feedback device current loop. 

If Analog Input 1 Mode (07.007) is set to any of the 4-20mA or 20-4mA modes and the current falls below 3mA then Analog Input 1 Current Loop Loss (07.028) is set to one. If the current is more than 3mA or any other mode is selected then Analog Input 1 Current Loop Loss (07.028) is set to zero.


Parameter07.029  Analog Input 2 Current Loop Loss (T6)
Short descriptionDisplays when analog input 2 falls below 3mA
ModeRFC‑S
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 1 Current Loop Loss (07.028).


Parameter07.030  Analog Input 1 Offset (T5)
Short descriptionDefines the offset of analog input 1
ModeRFC‑S
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

By default, analog input 1 T5 is routed to the Pump software analog feedback input parameter PID Feedback Percent (29.034).

See Analog Input 1 Scaling (07.008).


Parameter07.031  Analog Input 2 Offset (T6)
Short descriptionDefines the offset of analog input 2
ModeRFC‑S
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.033  Power Output
Short descriptionInstant output power
ModeRFC‑S
Minimum-100.0Maximum100.0
Default Units%
Type16 Bit VolatileUpdate Rate250µs write
Display FormatStandardDecimal Places1
CodingRO, ND, NC, PT

This is an instantaneous power output with fast update rate that is primarily intended to be used as a power feed-forward for applications with a Regen system front end. The full scale (100.0%) value is equal to a power of 3 x (VM_DC_VOLTAGE[MAX] / 2√2) x Full Scale Current Kc (11.061). This is compatible with the power output provided in Unidrive SP and is directly compatible with Regen Power Input on a regen capable Unidrive M (and the other power feed-forward parameters) in Regen mode. The scaling is intended to cover the maximum range of likely power in the drive. For example with a 400V 7.5kW drive the full scale d.c. link voltage is 831V and Kc=38.222A, and so the full scale value of this parameter is 3 x (831 / 2√2) x 38.222 = 33.689kW. For Open-loop, RFC-A and RFC-S modes a positive value of power indicates power flowing from the drive to motor. For Regen mode a positive value of power indicates power flowing from the supply to the regen drive.


Parameter07.034  Inverter Temperature
Short descriptionDisplays the estimated junction temperature of the hottest power device within the drive inverter
ModeRFC‑S
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (see Auto-switching Frequency Change (05.035)).


Parameter07.035  Percentage Of d.c. Link Thermal Trip Level
Short descriptionDisplays the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components
ModeRFC‑S
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of d.c. Link Thermal Trip Level (07.035) gives the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components. If the drive has multiple parallel power modules, the model for the d.c. link components is provided in each power module, and so this parameter will remain at zero.


Parameter07.036  Percentage Of Drive Thermal Trip Level
Short descriptionDisplays the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest
ModeRFC‑S
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of Drive Thermal Trip Level (07.036) gives the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest. This includes all thermal monitoring points (not just those selected by Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006)), Inverter Temperature (07.034) and Percentage Of d.c. Link Thermal Trip Level (07.035).

Percentage Of d.c. Link Thermal Trip Level (07.035) is used directly to give Percentage Of Drive Thermal Trip Level (07.036), but for all other monitored values which are temperatures this is given by Percentage of thermal trip level = (Temperature - 40oC) / (Trip temperature - 40oC) x 100%

The location of the measurement or the thermal model that is related to this temperature is given in Temperature Nearest To Trip Level (07.037). If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% Drive Over-temperature Alarm (10.018) is set to one. If Percentage Of Drive Thermal Trip Level (07.036) reaches 100% one of the trips given in the table below is initiated. The trip can be reset when the percentage of thermal trip level fall below 95%.

Temperature Trip
Inverter Temperature (07.034) OHt Inverter
Power system temperature OHt Power
Percentage Of d.c. Link Thermal Trip Level (07.035) OHt dc Link
Control system temperature OHt Control


Parameter07.037  Temperature Nearest To Trip Level
Short descriptionDisplays the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level
ModeRFC‑S
Minimum0
(Display: 00000)
Maximum20999
(Display: 20999)
Default Units 
Type16 Bit VolatileUpdate RateBackground write
Display FormatLead Zero PadDecimal Places0
CodingRO, ND, NC, PT

Temperature Nearest To Trip Level (07.037) shows the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level (07.036) in the form xxyzz as shown in the table below.

Source xx y zz
Control system 00 0 01: Control board thermistor 1
Control system 00 0 02: Control board thermistor 2
Control system 00 0 03: I/O board thermistor (or internal braking resistor in servo Drive)
Control system 00 1 00: Inverter thermal model
Control system 00 2 00: D.c. link thermal model
Control system 00 3 00: Braking IGBT thermal model
Control system 00 4 00: Rectifier thermal model
Power system 01 0 zz: Thermistor location defined by zz in the power system
Power system 01           Rectifier number zz: Thermistor location defined by zz in the rectifier


Parameter07.038  Temperature Monitor Select 1
Short descriptionDefines the temperature to be monitored in Monitored Temperature 1
ModeRFC‑S
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1001
(Display: 01001)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 1 (07.038) selects the temperature to be monitored in Monitored Temperature 1 (07.004). See Monitored Temperature 1 (07.004) for details.  


Parameter07.039  Temperature Monitor Select 2
Short descriptionDefines the temperature to be monitored in Monitored Temperature 2
ModeRFC‑S
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1002
(Display: 01002)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 2 (07.039) selects the temperature to be monitored in Monitored Temperature 2 (07.005). See Monitored Temperature 1 (07.004) for details. 


Parameter07.040  Analog Input 1 Minimum (T5)
Short descriptionDefines the minimum value for analog input 1
ModeRFC‑S
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.041  Analog Input 2 Minimum (T6)
Short descriptionDefines the minimum value for analog input 2
ModeRFC‑S
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.043  Analog Input 1 Maximum (T5)
Short descriptionDefines the maximum value for analog input 1
ModeRFC‑S
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.044  Analog Input 2 Maximum (T6)
Short descriptionDefines the maximum value for analog input 2
ModeRFC‑S
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.051  Analog Input 1 Full Scale (T5)
Short descriptionDisplays the full scale value of analog input 1
ModeRFC‑S
Minimum0Maximum65535
Default Units 
Type16 Bit Power Down SaveUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT, BU

See Calibrate Analog Input 1 Full Scale (07.025).


Parameter07.052  Temperature Monitor Select 3
Short descriptionDefines the temperature to be monitored in Monitored Temperature 3
ModeRFC‑S
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1
(Display: 00001)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 3 (07.052) selects the temperature to be monitored in Monitored Temperature 3 (07.006). See Monitored Temperature 1 (07.004) for details. 


Parameter07.053  Analog Input 1 Thermistor Type (T5)
Short descriptionDefines the thermistor type for analog input 1
ModeRFC‑S
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0DIN44082
1KTY84
3PT1000
4PT2000
5NI1000

Analog Input 1 Thermistor Type (07.053) selects the type of temperature feedback device used with Analogue Input 1 when Analog Input 1 Mode (07.007) is set up for temperature feedback mode. When a temperature feedback mode is selected 5V is applied to the output via a 3.3kΩ resistor to supply current through the temperature measurement device.


Parameter07.054  Analog Input 1 Thermistor Feedback (T5)
Short descriptionDisplays the measured resistance of analog input 1
ModeRFC‑S
Minimum0Maximum5000
Default UnitsΩ
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 1 Thermistor Feedback (07.054) shows the measured resistance.


Parameter07.055  Analog Input 1 Thermistor Trip Threshold (T5)
Short descriptionDefines the thermistor trip threshold for analog input 1
ModeRFC‑S
Minimum0Maximum5000
Default3300UnitsΩ
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Over-temperature detection becomes active for input 1 if Analog Input 1 Thermistor Feedback (07.054) > Analog Input 1 Thermistor Trip Threshold (07.055). Over-temperature becomes inactive for input 1 if Analog Input 1 Thermistor Feedback (07.054) < Analog Input 1 Thermistor Reset Threshold (07.056). If Analog Input 1 Mode (07.007) is 7 or 8 (i.e. tripping is enabled) an Thermistor.001 trip is initiated.


Parameter07.056  Analog Input 1 Thermistor Reset Threshold (T5)
Short descriptionDefines the thermistor reset threshold for analog input 1
ModeRFC‑S
Minimum0Maximum5000
Default1800UnitsΩ
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See  Analog Input 1 Thermistor Trip Threshold (07.055).


Parameter07.057  Analog Input 1 Thermistor Temperature (T5)
Short descriptionDisplays the temperature of the device based on the resistance to temperature characteristic for the specified device
ModeRFC‑S
Minimum-50Maximum300
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

If Analog Input 1 Mode (07.007) is set up to select temperature measurement then Analog Input 1 Thermistor Temperature (07.057) shows the temperature of the device, otherwise Analog Input 1 Thermistor Temperature (07.057) = 0.


Parameter07.058  Analog Input 2 Thermistor Type (T6)
Short descriptionDefines the thermistor type for analog input 2
ModeRFC‑S
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0DIN44082
1KTY84
3PT1000
4PT2000
5NI1000

Analog Input 2 Thermistor Type (07.058) selects the type of temperature feedback device used with Analogue Input 2 when Analog Input 2 Mode (07.011) is set up for temperature feedback mode. When a temperature feedback mode is selected 5V is applied to the output via a 3.3kΩ resistor to supply current through the temperature measurement device.


Parameter07.059  Analog Input 2 Thermistor Feedback (T6)
Short descriptionDisplays the measured resistance of analog input 2
ModeRFC‑S
Minimum0Maximum5000
Default UnitsΩ
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 2 Thermistor Feedback (07.059) shows the measured resistance.


Parameter07.060  Analog Input 2 Thermistor Trip Threshold (T6)
Short descriptionDefines the thermistor trip threshold for analog input 2
ModeRFC‑S
Minimum0Maximum5000
Default3300UnitsΩ
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Over-temperature detection becomes active for input 2 if  Analog Input 2 Thermistor Feedback (07.059) > Analog Input 2 Thermistor Trip Threshold (07.060). Over-temperature becomes inactive for input 2 if  Analog Input 2 Thermistor Feedback (07.059) <  Analog Input 2 Thermistor Reset Threshold (07.061). If Analog Input 2 Mode (07.011) is 7 or 8 (i.e. tripping is enabled) an Thermistor.002 trip is initiated.


Parameter07.061  Analog Input 2 Thermistor Reset Threshold (T6)
Short descriptionDefines the thermistor reset threshold for analog input 2
ModeRFC‑S
Minimum0Maximum5000
Default1800UnitsΩ
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See  Analog Input 2 Thermistor Trip Threshold (07.060).


Parameter07.062  Analog Input 2 Thermistor Temperature (T6)
Short descriptionDisplays the temperature of the device based on the resistance to temperature characteristic for the specified device
ModeRFC‑S
Minimum-50Maximum300
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

If Analog Input 2 Mode (07.011) is set up to select temperature measurement then Analog Input 2 Thermistor Temperature (07.062) shows the temperature of the device, otherwise Analog Input 2 Thermistor Temperature (07.062) = 0.


Parameter07.063  Analog Input 1 Filter Time Constant (T5)
Short descriptionDefines the time constant of the filter applied to Analogue Input 1.
ModeRFC‑S
Minimum0Maximum6
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Disabled
1500us
21ms
32ms
44ms
58ms
616ms

Unless the analogue input is set up in thermistor mode the update rate is 250us and with this parameter set to its default value no filtering is applied. This parameter can be modified from its default value to apply a first order filter to the input to remove noise. 


Parameter07.064  Analog Input 2 Filter Time Constant (T6)
Short descriptionDefines the time constant of the filter applied to Analogue Input 2.
ModeRFC‑S
Minimum0Maximum6
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Disabled
1500us
21ms
32ms
44ms
58ms
616ms

See Analog Input 1 Filter Time Constant (07.063).